|
The RoC form is required by all national codes and standards:
Mr. Kessinger's insight...
We sell the Record of Completion form:
Go to Shopping Cart for all products
Save yourself money, time and aggravation. The only way you can get these cheaper locally is to buy them 1,000 at a time. But, how can you justify paying the the printer's set-up fee, and their minimum order, just to trim 50¢ from our per-form cost of $3? You'll only end up paying more money, for more forms than you'll ever need, just to have them become outdated when the next edition of NFPA 72 comes out. Ten forms at a time at $3 each, is the way to go.
In the IFC has the requirement in 907.17. "A record of completion in accordance with NFPA 72 verifying that the system has been installed in accordance with the approved plans and specifications shall be provided."
In the IBC and OBC has the requirement in 907.17. "A record of completion in accordance with NFPA 72 verifying that the system has been installed in accordance with the approved plans and specifications shall be provided." (Note: the wording is identical in all four codes.) Return
The OFC has the same basic wording as the OBC except it is in 907.18. "A record of completion in accordance with NFPA 72 as listed in rule 1301:7-7-45 of the Administrative Code verifying that the system has been installed in accordance with the approved plans and specifications shall be provided."
Life Safety Code, 2006 edition. "9.6.1.5* To ensure operational integrity, the fire alarm system shall have an approved maintenance and testing program complying with the applicable requirements of NFPA 70, National Electrical Code, and NFPA 72, National Fire Alarm Code." Return
RECORD OF COMPLETION REQUIREMENTS FROM NFPA 72, 2002 edition: (Enforced by most states, including Ohio) 4.5 Documentation. 4.5.1 Approval and Acceptance. 4.5.1.1* The authority having jurisdiction shall be notified prior to installation or alteration of equipment or wiring. At the authority having jurisdiction’s request, complete information regarding the system or system alterations, including specifications, shop drawings, battery calculations, and notification appliance circuit voltage drop calculations shall be submitted for approval. 4.5.1.2 Before requesting final approval of the installation, if required by the authority having jurisdiction, the installing contractor shall furnish a written statement stating that the system has been installed in accordance with approved plans and tested in accordance with the manufacturer’s specifications and the appropriate NFPA requirements. 4.5.1.3* The record of completion form, Figure 4.5.2.1, shall be permitted to be a part of the written statement required in 4.5.1.2. When more than one contractor has been responsible for the installation, each contractor shall complete the portions of the form for which that contractor had responsibility. 4.5.1.4 The record of completion form, Figure 4.5.2.1, shall be permitted to be a part of the documents that support the requirements of 4.5.2.4. 4.5.2 Completion Documents. 4.5.2.1* Preparation. The preparation of a record of completion, Figure 4.5.2.1, shall be the responsibility of the qualified and experienced person described in 4.3.3 and shall be in accordance with 4.5.2.1(A) and 4.5.2.1(B). (A) Parts 1, 2, and 4 through 10 shall be completed after the system is installed and the installation wiring has been checked. Part 3 shall be completed after the operational acceptance tests have been completed. (B) A preliminary copy of the record of completion shall be given to the system owner and, if requested, to other authorities having jurisdiction after completion of the installation wiring tests. A final copy shall be provided after completion of the operational acceptance tests. 4.5.2.2 Revision. All fire alarm systems that are modified after the initial installation shall have the original record of completion revised to show all changes from the original information and shall include a revision date.
RECORD OF COMPLETION REQUIREMENTS FROM NFPA 72, 2007 edition: (Not yet widely adopted by building and fire codes.) 4.5 Documentation.
|
The Test and Inspection Record. The T&I form is required by national codes and standards:
Mr. Kessinger's insight...
We sell the Test and Inspection form:
Forms, records and other information must be kept in an "approved location." CLICK HERE to find out what else the codes require you to give the client when the fire alarm installation is finished.
Records of all system inspections, test, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and made available to the fire code official upon request. Return
"OFC 907.20.5 Maintenance, inspection, and testing. The building owner shall be responsible for ensuring that the fire and life safety systems are maintained in an operable condition at all times. Service personnel shall meet the qualification requirements of an NFPA 72 for maintaining, inspecting, and testing such systems. A written record shall be maintained and shall be made available to the fire code official." Return
10.6.2 Maintenance, Inspection, and Testing Records.
Section 907.20.5 of both the OFC and International Fire Code: Maintenance, inspection and testing. The building owner shall be responsible for ensuring that the fire and life safety systems are maintained in an operable condition at all times. Service personal shall meet the qualification requirements of NFPA 72 for maintaining, inspecting and testing such systems. A written record shall be maintained and shall be made available to the fire code official. Return
"Required by code, the Record of Completion form, a year's worth of Test/Inspection forms and Impairment Tags PLUS the OPTIONAL Warning Labels shown below will add about $15 to each of your commercial fire alarm installations. I know of no cheaper way of staying out of trouble and lessening your liability while improving your company's image." - GK |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||