Home NICET CD Software Fire Alarm Forms Fire Alarm Tags Security Dealer NBFAA

The following is also required to be provided to the client upon completion.  These items are not listed individually in the Building/Fire Codes, but are made mandatory when the Building/Fire Codes require compliance with NFPA 72.  (Ohio currently enforces the 2002 edition of NFPA 72, while the IBC/IFC both currently reference the 1999 edition.)

NFPA 72, 2002. Chapter Four  "4.5.2.3 Documentation Required.  Every system shall include the following documentation, which shall be delivered to the owner or the owner’s representative upon final acceptance of the system:
(1)* An owner’s manual and manufacturer's published instructions covering all system equipment
(2) Record drawings
(3) For software-based systems, a record copy of the site-specific software"

and Chapter Ten  "10.6 Records.   10.6.1* Permanent Records. After successful completion of acceptance tests approved by the authority having jurisdiction, the requirements in 10.6.1.1 through 10.6.1.3 shall apply.
10.6.1.1 A set of reproducible as-built installation drawings, operation and maintenance manuals, and a written sequence of operation shall be provided to the building owner or the owner’s designated representative.
10.6.1.2* For software-based systems, a copy of the site-specific software shall be provided to the owner or owner’s designated representative. A copy of the software shall be stored in non-volatile non-erasable, non-rewritable memory and shall be stored on-site.
10.6.1.3 The owner shall be responsible for maintaining these records for the life of the system for examination by any authority having jurisdiction. Paper or electronic media shall be permitted."

Why use a document cabinet?

bulletThe number one reason to spring for this cabinet is so there would be a place where the fire inspector could look to find all the test and inspection reports required by law.  If it is empty, expect a call from your client wanting to sign a Test and Inspection contract with you.  Yesterday.  These can pay for themselves many times over.
bullet A lot of paperwork is required to be kept by the building owner.  They will often lose this documentation you spent so much time and effort to generate.
bulletIt's professional.  You should not have these documents since the owner must prove compliance with the Fire Code.
bulletBesides  the last three years of T&I reports, you must store the required as-built drawings, Record of Completion form, a copy of site-specific software, and a copy of the sequence of operation.  This is also a great place to store the Owner's manual and specification sheets "for all equipment".

     FACP isn't accessible? Attach the tags to the cabinet!

(Fire Alarm Document cabinet available from  The security Source Inc., Cleveland, Ohio.)

Pop-quiz:

Does NFPA 72, section 10.2.2.2 in the  2002 edition, and section 10.2.4 of the 2007 edition,  both require that the owner supply you with all of the fire alarm system documentation required by Chapter Four and Chapter Ten? 

And what if your company didn't install the system originally?  (Answer below)

 

 

 

 

 

 

 

 

 

 

Answer:  BOTH editions use the same wording:   NFPA 72,  "System Documentation.  Prior to system maintenance or testing, the system certificate and the information regarding the system and system alterations, including specifications, wiring diagrams, and floor plans, shall be provided by the owner or a designated representative to the service personnel upon request." 

I doesn't matter who the original contractor was, these documents belong to the owner.